FVP 110 Fieldbus Valve Positioner Manual
208
GE Energy
41 8041 FF_SCALE 0-100% Man Scale limits used for converting the FF_VAL
value to a non-dimensional value.
42 8042 FF_GAIN 0 Man Gain for FF_VAL.
43 8043 UPDATE_EV
T
— – Shows the contents of an update event upon
occurrence.
44 8044 BLOCK_ALM — – Shows the contents of a block alarm upon
occurrence.
45 8045 ALARM_SUM Enable Shows the alarm summary (current alarm
statuses, acknowledged/unacknowledged
states, masking states)
46 8046 ACK_OPTIO
N
0XFFFF Selects whether or not the alarms related to the
DI block are automatically self-acknowledged.
47 8047 ALARM_HYS 0.5% Hysteresis for alarm detection and resetting to
prevent each alarm from occurring and
recovering repeatedly within a short time.
48 8048 HI_HI_PRI 0 Priority order of HI_HI_ALM alarm.
49 8049 HI_HI_LIM +INF Setting for HI_HI_ALM alarm.
50 8050 HI_PRI 0 Priority order of HI_ALM alarm.
51 8051 HI_LIM +INF Setting for HI_ALM alarm.
52 8052 LO_LO_PRI 0 Priority order of LO_ALM alarm.
53 8053 LO_LO_LIM +INF Setting for LO_ALM alarm.
54 8054 LO_PRI 0 Priority order of LO_LO_ALM alarm.
55 8055 LO_LIM +INF Setting for LO_LO_ALM alarm
56 8056 DV_HI_PRI 0 Priority order of DV_HI_ALM alarm.
57 8057 DV_HI_LIM +INF Setting for DV_HI_ALM alarm.
58 8058 DV_LO_PRI 0 Priority order of DV_LO_ALM alarm.
59 8059 DV_LO_LIM +INF Setting for DV_LO_ALM alarm.
Table 65 PID Block Parameters (Continued)
Relative
Index
Index Parameter
Name
Default
(factory
setting)
Write Description