5.2.3.2  Configuring the Laptop Computer and Perception software 
1.  In  Microsoft  Windows,  set  the  serial  port  to  which  the  RS-232  cable  is 
connected to the following values: 
•  Fixed  baud  rate  (must  be  identical  to  the  value  of  the  Setup  >  Comm 
Setup > DB9 Baud Rate Hydran M2-X parameter) 
•  data bits 
•  No parity 
•  1 stop bit 
•  No flow control 
Note:  In  Windows  for  example,  proceed  as  follows  to  access  the  serial  port 
settings:  log  on  as  administrator,  click  Start,  point  to  Settings,  click  Control 
Panel, double-click  System,  click  the  Hardware  tab, click  Device  Manager  and 
click Ports (COM & LPT). 
2.  Launch the Perception software.  
3.  In  Perception  under  the  properties  tab,  configure  the  communication 
parameters. 
5.2.3.3  Verifying the RS-232 Communications 
Proceed as follows: 
1.  Using the Perception software, verify that communication is established with 
the Hydran M2-X. If communication cannot be established, ensure  that the 
Hydran  M2-X  is  connected  to  the  appropriate  serial  port  on  the  laptop 
computer  and  that  it  has  the  proper  ID  and  baud  rate.  Confirm  good 
communications  in  the  Relays/Analog  window  of  the  Perception  software, 
change the Relay Mode of each relay from Force Off to Force On and back; 
this should toggle the state of the Hydran M2-X’s alarm relays. 
2.  After  the test,  in the Hydran  M2-X Host  software,  set the  Relay  Mode  of all 
relays back to Normal. 
 
5.2.4  Installing a Hydran 201i Controller 
1.  Install  a  Hydran 201Ci Controller (preferably  a  Hydran 201Ci-C  or  a Hydran 
201Ci-1) equipped with an internal modem (optional; available from General 
Electric).    For  details  on  how  to  install  a  Hydran  201Ci  Controller,  see  the 
Hydran 201i System Instruction Manual. 
Note:    Electrical  noise is  one  of the  most  important factors  when  selecting  the 
location and installing a modem. Ideally, the Hydran 201Ci Controller should be 
located  in  a  limited  zone  of  an  electrical  substation  (for  example,  the  control 
room). 
2.  If  necessary,  connect  the  Hydran  201Ci  Controller  to  its  modem  using  the 
supplied cable.  The reception (Rx) and transmission (Tx) pins of this cable are 
not criss-crossed.