8.4.6  Moisture Readings Remain at 0% 
Probable causes: 
1.  If there is no display (see Figure 3-1), the 24-Vdc power supply of the Hydran 
M2-X has failed.  Verify the wiring at both ends of the dc power supply cable. 
2.  The analog output cable is disconnected or broken. 
 
8.4.7  Irregular Readings (Moisture and Temperature) 
On a transformer in operation, it is normal to observe variations in the moisture 
of the oil.   This parameter is sensitive to the  temperature as  the quantity of water 
that can be absorbed by the oil increases logarithmically with the temperature.  For 
a  constant  water  concentration  (ppm),  the  moisture  drops  rapidly  as  the  oil 
temperature rises.  For example, in a relatively dry transformer (1 % moisture in the 
paper), a 15 °C (27 °F) variation between day and night can produce a variation in 
moisture of 2 to 3 %; this effect is stronger in a wet transformer.  The oil warming 
causes a reduction of its moisture, thus resulting in a water transfer from the paper 
into the oil.  When the oil is hot (70–100 °C [158–212 °F]), this transfer is significant 
and contributes to stabilize the moisture reading; at low temperatures, this transfer 
is very slow and has a low impact over a 24-hour cycle. 
The  probable  cause  of  irregular  readings  is  electric  interference.    Verify  the 
grounding and shielding of the analog output cable.