-  CableShort; SysOK Relay;FaultTrig. submenu; see Section 3.2.3. 
-  No set point nor delay. 
•  Alarm cause(s): Faulty connection with one of the following cables:  
-  Sensor cable. 
-  Sensor thermistor cable (reading of 200 °C during one minute). 
-  Heater plate thermistor cable (reading of 200 °C during one minute). 
Proceed as described for the Gas C.Open Alarm (see Section 8.1.7), but replace all 
mentions of “-75 °C” with “200 °C”. 
 
8.1.9  Gas Sens. Bad Alarm 
•  Alarm type:  Due to system fault conditions. 
•  Non-abbreviated description:  Replace sensor now. 
•  Alarm message on thePerception software:  H2 Sensor Test Bad. 
•  Priority:  Very high. 
•  Parameter(s) involved:  
-  SensRep Now; SysOK Relay;FaultTrig. submenu; see Section 3.2.3. 
-  No set point nor delay. 
•  Alarm cause(s):  The sensor sensitivity has dropped significantly or the sensor 
is not functioning. 
Replace the sensor as soon as possible. 
Note:  The Hydran M2-X’s sensor is verified twice a month (the first and fifteenth 
days  of  the  month  at  midnight);  the  relevant  parameters  are  recorded  in  the 
Service  history  file.    This  test  can  also  be  performed  manually  using  the  Force 
Sensor  Test  command  (in  the  Service  submenu),  but  no  results  are  recorded.  In 
both  cases,  one  of  the  following two  messages is  displayed if  the  test  fails:  Gas 
Sens. Weak Alr or Gas Sens. Bad Alr. 
 
8.1.10  S. Card Comm Err Alarm 
•  Alarm type:  Due to system fault conditions. 
•  Non-abbreviated description:  Communication error alarm. 
•  Alarm message on thePerception software:  Sensor Comm. Failure. 
•  Priority: High. 
 
8.1.11  S. Temp C. Open Alarm 
•  Alarm type:  Due to system fault conditions. 
•  Non-abbreviated description:  Low-Low sensor temperature. 
•  Alarm message on the Perception software:  Sensor Temp Cable Open. 
•  Priority: High.