5.  Perform the verification procedure described in Section 4.2.9. 
 
4.4.9  Verifying the Sensor 
1.  Access Service > Sensor Test (see Section 3.5.1).  
2.  Press  Ok  to  start  the  test.    After  a  few  seconds,  the  Hydran  M2-X’s  display 
should show message Testing Success.  If another message is displayed, see 
Section 8.1. 
Note:  The keypad cannot be used for two minutes following a sensor test.  
Wait before resuming the configuration. 
 
4.4.10  Setting the Operation Mode of the Alarm Relays 
For details on relays operation, see Section 6.5; for details on operation modes of 
relays, see Section 6.5.3. 
1.  Access Test > Relay Test (see Section 3.5.2). 
2.  Verify and set, as required, the operation mode of each relay.  
3.  Verify  the  relay  status  is  properly  monitored  by  the  SCADA  or  annunciator 
system. 
 
4.4.11  Verifying the Sensor Parameters 
1.  Access Service > Sensor Param > Gas Sensor Param (see Section 3.6.1.1). 
2.  Make sure the displayed serial number, the ten parameters (B, M, N, S and A1 
to A6) and the checksum all correspond to the values on the Test Certificate 
and Data Sheet (for an example, see Figure 3-12). 
3.  Press Esc and access H2O Sensor Param (see Section 3.6.1.2). 
4.  Make sure the displayed serial number, the  ten parameters (C1 to C10) and 
the checksum all  correspond to the  values on the Test Certificate and Data 
Sheet. 
 
4.4.12  Logging Values of the Service Data 
1.  Access Service > View Service Data.  
2.  Write the values of each parameter in Table B - 5.