Hydran* M2-X Instruction Manual
MA-029 Rev. 1.0, 30-Jul-18
Parameter(s) involved:
- SensTemp LL; SysOK Relay;FaultTrig. submenu; see Section 3.2.3.
- STempAlr LL (alarm set point); Temperature submenu; see Section 3.3.2.1.
- TempoAlr Delay; Temperature submenu; see Section 3.3.2.1.
Alarm cause(s): Temperature of the sensor below the Alarm Lo-Lo SP alarm
set point
The sensor sensitivity is very low; repair the Hydran M2-X’s dynamic oil sampling
system.
8.1.12 S. Temp Hi Alarm
Alarm type: Due to system fault conditions.
Non-abbreviated description: High sensor temperature.
Alarm message on the Perception software: Sensor Temp High.
Priority: High.
Parameter(s) involved:
- SensTemp H; SysOK Relay;FaultTrig. submenu; see Section 3.2.3.
- Alarm Hi SP (alarm set point); Temperature submenu; see Section 3.3.2.1.
- TempoAlr Delay; Temperature submenu; see Section 3.3.2.1.
Alarm cause(s): Temperature of the sensor above the Alarm Hi SP alarm set
point.
Although the sensor is not affected by the temperature, monitor its temperature
regularly.
8.1.13 S. Temp Low Alarm
Alarm type: Due to system fault conditions.
Non-abbreviated description: Low sensor temperature.
Alarm message on the Perception software: Sensor Temp Low.
Priority: High.
Parameter(s) involved:
- SensTemp L; SysOK Relay;FaultTrig. submenu; see Section 3.2.3.
- STempAlr L (alarm set point); Temperature submenu; see Section 3.3.2.1.
- TempoAlr Delay; Temperature submenu; see Section 3.3.2.1.
Alarm cause(s): Temperature of the sensor below the Alarm Low SP alarm set
point.
Although the sensor is not affected by the temperature, monitor its temperature
regularly.
8.1.14 S. Tmp C. Short Alarm