6.2.5.4  Guidelines for Setting Alarm Conditions of Gas Trends 
Hourly  and daily  trend High  and  High-High alarm  condition settings cannot  be 
described in terms of absolute criteria.  They are related to the user’s field experience 
and the utility’s standard practice.  This Section provides a few guidelines to optimize 
both the hourly and daily trend alarm conditions. 
1.  The  readings  of  the  Hydran  M2-X  should  be  monitored  over  a  minimum 
period of two to three times the trend period before setting these parameters.  
Follow  the  same  rules  as  for  the  gas  level  High  alarm  condition  listed  in 
Section 6.2.4. 
2.  If a fast response to a sudden gas level increase is needed, it is best to rely on 
the gas level alarm conditions rather than on trend alarm conditions.  Trend 
alarm  conditions  are  ideal  to  detect  slow  and  steady  changes  from 
fluctuating readings, but are not as good to detect abrupt changes. 
3.  The  transformer  (or  other  equipment)  past  history  and  the  user’s  field 
experience  are  the  most  important  criteria  for  alarm  condition  settings.    If 
existing, records of previous dissolved  gas analysis (DGA) for the equipment 
monitored  should  be  used  to  help  determine  alarm  condition  settings  in 
general and especially for the daily trend. 
4.  Trend  alarm  delays  should  be  set  according  to  each  trend  period  (see 
guidelines in Section 3.2.8.1). For example:  
•  If the hourly trend period is set to four hours, the hourly trend reading may 
show quite large, but short, positive and negative peaks during a day. In 
this case, an hourly trend alarm delay of 50 to 75 % of the period could 
avoid unnecessary alarms. 
•  However,  if  the hourly  trend period is  set to 48 hours, daily  fluctuations 
would  not  affect  the  trend  reading  significantly.  In  this  case,  the  alarm 
delay could be set to 10 to 20 % of the period. 
 
6.3  System Fault Conditions 
An alarm due to system fault conditions warns the operator that the Hydran M2-
X is not functioning properly. Such an alarm must  therefore be verified and solved 
rapidly  because  it  indicates  that  the  monitoring  system  (the  Hydran  M2-X)  of  the 
transformer is faulty. 
Note:  An alarm due to system fault conditions does not concern the transformer.