6.2.1  Sources 
Alarms can be triggered by one or several of the following sources: 
•  Gas sources: 
  Hydran level:  This value is measured by the Hydran M2-X gas detector. 
  Hydran hourly trend:  This value is calculated based on the variation of 
gas  level  during  a  period  of  time  ranging  from  1  to  100  hours.    The 
hourly trend is updated every five seconds. 
  Hydran daily trend:  This value is calculated based on the variation of 
gas level during a period of time ranging from 1 to 100 days.  The daily 
trend is updated every five minutes. 
 
•  Moisture sources: 
  Relative  humidity  (%RH)  level:   This value  is  measured  by  the  Hydran 
M2-X moisture sensor.  
  Relative humidity (%RH) hourly average:  This value is calculated based 
on  the  relative  humidity  calculations  made  during  a  period  of  time 
ranging from 1 to 170 hours.  The relative humidity average is updated 
every five seconds.  
  Moisture (H
2
O ppm) level:  This value is calculated based on the relative 
humidity (%RH) and the temperature (see Section K-2). 
  Moisture (H
2
O ppm) hourly average:  This value is calculated based on 
the moisture level readings obtained during a period of time ranging 
from 1 to 170 hours.  The average moisture level is updated every five 
seconds. 
6.2.2  High and High-High Conditions 
The High and High-High alarm conditions are defined as follows: 
•  High alarm  conditions: High conditions are set at a lower value than the 
corresponding High-High conditions. They are caution signs; set points for 
High  alarm  conditions  should  be  set  at  values  that  indicate  that  the 
transformer (or other equipment) requires closer monitoring.  
•  High-High  alarm  conditions:  High-High  conditions  are  set  at  a  higher 
value. They are warning signs; set points for High-High alarms should be 
set  at  values  considered  as  critical  by  the  user,  meaning  that  the 
transformer  requires  immediate  action  according  to  standard  utility 
procedures. In general, this alarm implies an evaluation of the equipment 
and its possible removal from service.  
Note: Each analog input could also generate four alarm conditions:  Low-Low, 
Low, High and High-High.