Hydran* M2-X Instruction Manual
MA-029 Rev. 1.0, 30-Jul-18
Sensor Temp Avg.: Average temperature of the sensor, in °C. The period used to
calculate this value is set with parameter Sens. Temp Avg Per. in Setup >
Readings Setup (see Section 3.2.8.3).
H
2
O Cell mV: Voltage of the electrical signal currently sent by the moisture
sensor.
3.4.2 View History Data
The Hydran M2-X has an internal function that automatically records information
such as gas and moisture levels, trend values, alarm messages and setup
parameters. This information is stored in four sections, which are collectively referred
to as history files.
The View History Data functions are used to consult the four history files:
Short Term (recording at a fixed logging rate; example: every 15 minutes)
Long Term (recording at fixed logging rates; example: each day at midnight)
Events (recording at the time of events; example: alarms)
Service (recording at the time of the semimonthly, automatic sensor test)
The maintenance procedure in Section 9 shows how the data of the history files
can be used.
3.4.2.1 Short Term History
The Short Term History function gives access to the Short Term history file. From
1 to 360 minutes (adjustable; see parameter Short Term Rate in Setup > History
Setup > History Log Rate [see Section 3.2.6.1]), the date and time plus several values
are logged in this file. Its capacity is 4,760 records (if equipped with four analog input
inter-faces); when the file is full, a new record erases the oldest one in a first in, first
out method.
The following variables are recorded in the Short Term history file (this list is
identical for the Long Term and Event history files):
Gas level in ppm.
Service U.
Hourly trend in ppm/x hours (default value is 24 hours).
Daily trend in ppm/x days (default value is 30 days).
Service V.
Relative humidity level in %.
Relative humidity average in %/x hours.
Moisture level in ppm.
Moisture average in ppm/x hours.
H
2
O cell signal in V (microvolts).
Heater plate temperature in ˚C.
Heater plate output power in percentage.
Sensor temperature in ˚C.

Table of Contents

Other manuals for GE Hydran M2-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Hydran M2-X and is the answer not in the manual?

GE Hydran M2-X Specifications

General IconGeneral
BrandGE
ModelHydran M2-X
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals