Hydran* M2-X Instruction Manual
Page 126
MA-029 Rev. 1.0, 30-Jul-18
- Batt. L; SysOK Relay;FaultTrig. submenu; see Section 3.2.3.
- Batt.Alr L (alarm set point); Service;VoltPile submenu; see Section 3.3.2.4.
- BattAlr Delay; Service;VoltPile submenu; see Section 3.3.2.4.
Alarm cause(s): Battery voltage below the Alarm Low SP alarm set point.
Replace the battery within the next nine months. For details, see Appendix G.
8.1.3 B.P. Temp Hi Alarm
Alarm type: Due to system fault conditions.
Non-abbreviated description: High base plate temperature.
Alarm message on the Perception software: Base Plate Temp High.
Priority: High.
Alarm cause(s): Temperature of the base plate above the Alarm Hi SP alarm
set point.
8.1.4 B.P. Temp Low Alarm
Alarm type: Due to system fault conditions.
Non-abbreviated description: Low base plate temperature.
Alarm message on the Perception software: Base Plate Temp Low.
Priority: High.
Alarm cause(s): Temperature of the base plate below the Alarm Low SP alarm
set point.
8.1.5 B.P. Tmp C. Open Alarm
Alarm type: Due to system fault conditions.
Non-abbreviated description: Low-Low base plate temperature.
Alarm message on the Perception software: Base Plate Temp Cable Open.
Priority: High.
Alarm cause(s): Temperature of the base plate below the Alarm Lo-Lo SP
alarm set point.
8.1.6 B.P. Tmp C. Short Alarm
Alarm type: Due to system fault conditions.
Non-abbreviated description: High-High base plate temperature.
Alarm message on the Perception software: Base Plate Temp Cable Short.
Priority: High.