EasyManua.ls Logo

GE Hydran M2-X - Alarm Relays

GE Hydran M2-X
204 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 117
Hydran* M2-X Instruction Manual
MA-029 Rev. 1.0, 30-Jul-18
Note: To cancel an alarm condition that has an alarm delay, the alarm condition
that triggered the alarm must disappear during a period of time exceeding its
alarm delay.
4. Verify if the alarm condition is listed in the Main Display mode (see
Section 3.1.2.3). If present, the problem was not corrected; start over from
step 1.
6.5 Alarm Relays
The Hydran M2-X has five alarm relays. Typically the relays are assigned to alarm
conditions as follows:
Relay 1 to gas High alarm conditions
Relay 2 to gas High-High alarm conditions
Relay 3 to moisture High alarm conditions
Relay 4 to moisture High-High alarm conditions
Relay 5 to system fault conditions (this relay cannot be reassigned)
Note: Several conditions can be assigned to one alarm relay.
6.5.1 Alarm Contacts
Each relay has:
A normally open (NO) contact
A normally closed (NC) contact
A common contact (type C)
Table 6-9 below lists the possible states of the alarm contacts.
Off
On
NO contact
Contact open
Contact closed
NC contact
Contact closed
Contact open
Table 6-9: Possible Sates of the Alarm Contacts
All contacts are available on the alarm terminal block. See Figure 2-6.

Table of Contents

Other manuals for GE Hydran M2-X

Related product manuals