Hydran* M2-X Instruction Manual
MA-029 Rev. 1.0, 30-Jul-18
Table B - 5: Logging the Values of the Analog Input Alarm Setup Parameters
Configuring the Analog Output(s) (If Used)
1. Configure the optional analog output(s)
2. Check the optional analog output(s)
1. Manual test of sensor operation is good?
Setting the Operation Mode of the Alarm Relays
Set Relay #1 Mode to Normal [ ] Latch [ ] Force On [ ] Force Off [ ]
Set Relay #2 Mode to Normal [ ] Latch [ ] Force On [ ] Force Off [ ]
Set Relay #2 Mode to Normal [ ] Latch [ ] Force On [ ] Force Off [ ]
Set Relay #4 Mode to Normal [ ] Latch [ ] Force On [ ] Force Off [ ]
Verifying the Sensor Parameters
1. Gas detector parameters correspond to those on Test Certificate
2. Moisture sensor parameters correspond to those on Test Certificate
Logging Values of the Service Data
Table B - 6: Logging the Values of the Service Data
Resetting the Hourly Trend, Daily Trend and Period B
1. Set Hourly Tr. Period to 1 hour
2. Set Daily Tr. Period to 1 day
3. Set Hydran PPM Period B to 0 hour
5. Set the above parameters to their default value (24 hours, 30 days and 24
hours)
Fasten the Hydran M2-X’s cover