Hydran* M2-X Instruction Manual 
 
MA-029  Rev. 1.0,  30-Jul-18 
 
1.  Wait at least two hours 
2.  Verify the reading accuracy using a DGA 
Installing the RS-485 Network Link 
1.  Run the cables through conduits to form a daisy chain 
2.  Ground conduit where cable is connected to RS-485 In terminals 
3.  Isolate conduit where cable is connected to RS-485 Out terminals 
4.  Ensure all wires are identified at both ends 
5.  Connect the wires to the RS-485 terminal blocks 
6.  The shield of each cable section is grounded at one end only 
Configuring the Hydran M2-X’s Communication Parameters 
1. No alarm condition detected 
2.  Set identification numbers: 
•  Set Power Station ID to _________ 
•  Set Monitor ID to _________ 
3.  Set communication parameters: 
•  Set DB9 Baud Rate to _________ bps 
•  Set 485 Baud Rate to _________ bps (identical for all Hydran M2-X’s) 
•  Set Comm Mode to Answer Only or [   ] Call on Alarm [   ] 
•  Set RS232<->RS485 to Disabled [   ] 
Installing and Configuring a Laptop Computer 
Connecting a Laptop Computer 
1.  Remove the cover of any Hydran M2-X in the network 
2.  Connect the RS-232 cable to the Hydran M2-X 
3.  Connect the RS-232 cable to the laptop computer’s serial ports 
Configuring the Laptop Computer and Perception software 
1.  Set the serial port’s baud rate and other parameters (8 data bits; no parity; 1 
stop bit; no flow control) 
Verifying the RS-232 Communications 
1.  Using Perception software verify that the communication can be established 
with the Hydran M2-X 
Installing a Hydran 201i Controller 
1.  Install a Hydran 201Ci Controller equipped with a modem 
2.  If necessary, connect the Hydran 201Ci Controller to its modem