Hydran* M2-X Instruction Manual
Page 176
MA-029 Rev. 1.0, 30-Jul-18
Terminal
Description
From (External)
Comments
L
Line
Live side of AC supply
AC supply is 110Vac ±15%
or 230Vac ±15% and from
47 to 63Hz. Maximum
load is 4A.
N
Neutral
Other side of AC supply
Enclosure
ground
(Earth)
Unless otherwise required
by the application local
regulations, the ground wire
from the power supply
cable must not be
connected to this terminal
Use external ground lug
instead
a
Table D - 4: Connections for the AC Power Supply Terminal Block
1. Connect a ground wire to the external terminal lug. Use a 10-6 AWG (approximately 5.3 13.3
mM2-X) copper wire.
Not connecting the ground terminal will cause operational
failure.
WARNING