Hydran* M2-X Instruction Manual
Page 178
MA-029 Rev. 1.0, 30-Jul-18
Terminal
a
Relay
b
Description
c
To (External)
Comments
1
1
NO
SCADA system, Hydran
201Ci-1 or Hydran
201Ci-4
User-configurable;
normally assigned to
gas High alarms
2
Common
3
NC
4
2
NO
User-configurable;
normally assigned to
gas High-High alarms
5
Common
6
NC
7
3
NO
User-configurable;
normally assigned to
moisture High alarms
8
Common
9
NC
10
4
NO
User-configurable;
normally assigned to
moisture High-High
alarms
11
Common
12
NC
13
5
NO
Not configurable;
used only for alarms
due to system fault
conditions; NO is
closed if system is OK,
NC is open if system
fails
14
Common
15
NC
Table D - 5: Connections for the Alarm Contacts Terminal Block
a. Designed for 16-14 AWG (1.37-2.03 mM2-X) wires
b. Electric specifications for all relays: 125 VA @ 250 Vac, 60 W @ 220 Vdc
c. NC = Normally Closed (contact is closed when the relay is not energized);
NO = Normally Open (contact is open when the relay is not energized)

Table of Contents

Other manuals for GE Hydran M2-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Hydran M2-X and is the answer not in the manual?

GE Hydran M2-X Specifications

General IconGeneral
BrandGE
ModelHydran M2-X
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals