The  Moisture  Alarm  Setup  functions  give  access  to  the  parameters  of  the 
moisture alarm conditions: 
•  %RH Level Alarm:  Gives access to the %RH moisture level High and High-High 
alarm parameters: 
–  Alarm Hi SP:  Set point of the relative humidity High alarm condition. 
–  Alarm Hi-Hi SP:  Set point of the relative humidity High-High alarm condition. 
–  Alarm Delay:  Alarm delay for both set points. 
–  Alarm  Hi  Relay:    Relay  activated  when  a  relative  humidity  High  alarm 
condition is detected. 
–  Alarm Hi-Hi Relay:  Relay activated when a relative humidity High-High alarm 
condition is detected. 
•  H2O PPM Level Alarm:  Gives access to the ppm moisture level High and High-
High alarm parameters: 
–  Alarm Hi SP:  Set point of the ppm moisture level High alarm condition in ppm. 
–  Alarm Hi-Hi SP:  Set point of the ppm moisture level High-High alarm 
condition in ppm. 
–  Alarm Delay:  Alarm delay for both set points. 
–  Alarm Hi Relay:  Relay activated when a moisture level High alarm condition 
is detected. 
–  Alarm  Hi-Hi  Relay:  Relay activated when a  moisture level  High-High alarm 
condition is detected. 
•  %RH Hourly Average Alarm:  Gives access to the relative humidity average High 
and High-High alarm parameters:  
–  Alarm Hi SP:  Set point of the relative humidity average High alarm condition. 
–  Alarm Hi-Hi  SP:  Set point of the relative humidity average High-High alarm 
condition. 
–  Alarm Delay:  Alarm delay for both set points. T his delay is calculated using 
parameter %RH  Average in Setup  >  Reading  Setup  >  H2O  Reading Setup; 
see Section 3.2.8.2. 
–  Alarm Hi Relay:  Relay activated when a relative humidity average High alarm 
condition is detected. 
–  Alarm Hi-Hi  Relay:  Relay activated when a relative humidity average High-
High alarm condition is detected. 
•  H2O  PPM  Hourly  Average  Alarm:    Gives  access  to  the  average  ppm  moisture 
level High and High-High alarm parameters:  
–  Alarm Hi SP:  Set point of average ppm moisture level High alarm condition in 
ppm. 
–  Alarm  Hi-Hi  SP:    Set  point  of  average  ppm  moisture  level  High-High  alarm 
condition in ppm. 
–  Alarm Delay:  Alarm delay for both set points.  This delay is calculated using 
parameter PPM H2O  Avg. in Setup  > Reading Setup  > H2O  Reading Setup; 
see Section 3.2.8.2. 
–  Alarm Hi Relay:  Relay activated when an average moisture level High alarm 
condition is detected. 
–  Alarm  Hi-Hi  Relay:    Relay  activated  when  an  average  moisture  level  High-
High alarm condition is detected.