152 GE INFORMATION D400 SUBSTATION GATEWAY INSTRUCTION MANUAL
CHAPTER 12: USING THE D400 LOCAL CONFIGURATION UTILITY
Table 44: Sync Set Example 1
Table 45: Sync Set Example 2
Check and rsync
Interval
The amount of time, in seconds, that the
Sync Manager waits before checking the
source path for changes. If changed or
created files are detected, an rsync
operation is triggered.
60 to 86400 seconds
Forced rsync
Interval
The amount of time, in seconds, that the
Sync Manager waits before a forced rsync
operation is triggered, regardless of
detected changes.
This recreates files that have been deleted
from the remote device as well as forcing
the transfer of files whose changes may not
have been detected due to MD5 collision, an
extremely rare occurrence.
60 to 86400 seconds
Field Value
Sync Set ID 1
Destination IP Address 192.1681.1
Destination User Name admin
Source Path Name /mnt/datalog/arrm
Destination Path Name /cygdrive/c/Stations_Data
Check and rsync Interval 60
Forced rsync Interval 60
Field Value
Sync Set ID 2
Destination IP Address 192.1681.2
Destination User Name admin
Source Path Name /mnt/datalog/arrm
Destination Path Name /cygdrive/c/Stations_Data/GW/Station_1/
D400_Name_1%D400_DESIGNATION
Where, %D400_DESIGNATION is the place holder for D400
Designation i.e. _A or _B.
For the above example, the destination path is:
For D400A:
/cygdrive/c/Stations_Data/GW/Station_1/D400_Name_1_A
For D400B:
/cygdrive/c/Stations_Data/GW/Station_1/D400_Name_1_B
Check and rsync Interval 60
Forced rsync Interval 60
Setting Description Range