10.3 IEC61850-3 Certification
10.3.1 Dielectric
Description Test Standard Mode Group Test Level
Impulse voltage
IEC 60255-27:2013
IEC 61180-1:1992
DC and AC Power ports
Binary input/output
Alarm output
5kV+0%,-10% - 1.2/50µs
impulse
Signal ports (RJ45 + serial
com)
1kV 1.2/50µs impulse
Dielectric voltage IEC 60255-27:2013
DC and AC Power ports
Binary input/output
Alarm output
2kV rms. 50Hz for 1 minute
Signal ports (RJ45 + serial
com)
0,5kV rms. 50Hz for 1
minute
Insulation resistance IEC 60255-27:2013 Earth and all others
Power, input/output,
Alarm and serial ports
Test voltage 500Vdc
Protective bonding
resistance
IEC 60255-27:2013 Mechanical ports
60s, Test voltage < 12Vdc or
12 Vrms ac
10.3.2 Electromagnetic Compatibility
10.3.2.1 Standard compliance
Reason H49 is compliant with European Commission Directive on EMC (IEC 61000-5
standard).
10.3.2.2 DC Auxiliary supply
Description Test Standard Group Test Level
DC voltage interruptions
IEC 61000-4-29:2000
IEC 60255-26:2013
DC Power port
Supply Interruptions
ΔU 100% for 50ms
DC voltage dips
IEC 61000-4-29:2000
IEC 60255-26:2013
DC Power port
ΔU 30% for 100ms,
ΔU 60% @ 100ms
Voltage ripple on DC Power Supply voltage
IEC 61000-4-17:2009
IEC 60255-26:2013
DC Power port
AC 100Hz ripple superimposed on
DC max. and min. auxiliary supply
at 10% of rated DC value.
Burden for DC Power supply DC Power port
PSU 110Vdc/load = Max 16,79VA
PSU 220Vdc/load = Max 16,79VA
Inrush current and power-up duration DC Power port
PSU 110Vdc = 19,4A (110 ms)
PSU 220Vdc = 43,8A (92 ms)