10.4 IEEE1613 Certification
Description Test Standard Mode Group Test Level
Service conditions IEEE C37.90:2007 - B8 Device Installation Zone A
Operational temperature range IEEE C37.90:2007 - B8
Device
Operating temperature: -25°C to
55°C
Storage temperature: -40°C to 70°C
Relative humidity
Device
55% (for op and no-op temperature)
with excursions up to 95% without
internal condensation for a
maximum of 96 h
Allowable ac component in dc
control voltage supply
DC Power port
Alternating component (ripple) of 5%
peak or less in the dc control voltage
supply, provided the minimum
instantaneous voltage is not less
than 80% of rated voltage
DC rated control power inputs
DC Power port
Operating successfully over a
minimum range of 85% to 110% of
rated voltage at rated frequency
AC rated control power inputs
AC Power port
Operating successfully over a
minimum range of 85% to 110% of
rated voltage at rated frequency
Dielectric power frequency
DC and AC Power
ports
Binary input/output
Alarm output
2kV, AC between 45Hz and 65Hz,
1min
Signal ports (RJ45 +
serial com)
500V, AC between 45Hz and 65Hz,
1min
Impulse voltage
DC and AC Power
ports
Binary input/output
Alarm output
a) Waveform polarity: Positive and
negative
b) Rise Time: 1.2 μs ± 30%
c) Magnitude: 5 kV +0/–10% (circuit
rated upper 50V)
d) Time to half value: 50 μs ± 20%
e) Source impedance: 500 Ω ± 10%
f) Output energy: 0.5 joules ± 10%
Fast transient waveform
IEEE C37.90:2007 - B8 CM
Power, Input /
output, Data com
and signal ports
4kV crest value (tolerance ± 10%)
IEEE C37.90:2007 - B8 TM
Power and output
ports
4kV crest value (tolerance ± 10%)
IEEE C37.90:2007 - B8 TM Watchdog 4kV crest value (tolerance ± 10%)