PTP Configuration
Figure 43: Reason H49 Web User Interface – PTP Settings
Set the PTP settings as detailed below:
Attribute Description Factory Default
Clock Mode
Use the drop-down list to select the PTP switching
mode:
• Disable
• Boundary clock
• Transparent clock - E2E
• Transparent clock - P2P
Transparent clock -
E2E
Slave Only
Set Reason H49 as a PTP slave-only. It means that
the device will not postulate as time master during
a selection campaign.
Enabled
Domain Enter the PTP domain between 0 and 255 0
Priority 1
Enter the priority level to turn the H49 as the
Master clock. Priority 1 goes from 0 to 255.
Lowest values increase the probability for the
device to be elected Master clock.
255
Priority 2
Enter the priority level to turn the H49 as the
Master clock. Priority 2 goes from 0 to 255.
Lowest values increase the probability to be
elected Master clock.
255
Step Number Select the device’s step synchronization mode. One-step
Profile
Selects the PTP profile
• Default L2
• Power profile
Power Profile