7.4.2.4 Priority
Reason H49 provides a mechanism for priorizing Ethernet frames by using Priority
Code Points.
Four priority queues (from 0 to 3) are present in Reason H49 (3 being the highest
priority) and eight Priority Code Point (PCP) can be distributed among the queues.
To configure priority queues, click Network > Priority.
Figure 78: Reason H49 Web User InterfacePriority Configuration
Set the priority mechanism as described below:
Attribute Description
Queue 0 to Queue 3
Select the queue for which the PCP is set.
A given queue can be associated with 0 or more PCPs
PCP0 to PCP7
Priority Code Point (PCP)
Only one Queue can be selected for each row.
C
lick the Default Values button to reset the H49 to factory defaults:
Queue 3: PCP6 ; PCP7
Queue 2: PCP4 ; PCP5
Queue 1: PCP2 ; PCP3
Queue 0: PCP0 ; PCP1