127
Electrostatic discharge tests IEEE Std C37.90.3:2012 - B4
Enclosure port
a) Contact discharge
(direct/indirect) = 8 kV
b) Air discharge (direct) = 15 kV
Immunity to conducted
disturbances induced by RF
fields
IEC 61000-4-6:2003 - 5
DC and AC Power ports,
earth port, signal ports
Level 3: 10Vemf
Power frequency magne
tic field
immunity tests
IEC 61000-4-8:1993
Enclosure port
Zone A:
100A/m continuous (≥60s)
1000A/m - 3s
Damped oscillatory magnetic
field tests
IEC 61000-4-10:2001
Enclosure port
Level 5:
100A/m peak
Applied in all planes at:
100kHz, repetition rate ≥
40Hz,
during 60s
1MHz, repetition rate ≥ 400Hz,
during 60s
Immunity to common-mode
disturbances
IEC 61000-4-16:2002
DC/AC Power port,
Signal ports
Level 4:
30 Vrms cont.
300 Vrms for 1 s
Frequency range = 0Hz to
150kHz
Coupling resistor 200Ω and
coupling capacitor 1uF - DC
and inputs
Coupling resistor 50Ω -
Ethernet ports
AC main frequencies - 50 Hz
and 60 Hz.
Vibration
Enclosure port
Class: V.S.2
Velocity: <10mm/s
Freq range 1Hz to 150Hz
Shock Enclosure port Height of fall : 100mm
Device cooling
Device shall be convection
cooled and shall not include
internal fans or any other
means of forced air circulation.