GE Reason H49
88
H49/EN M/C22
Earth Continuity Check
Using a continuity tester or Digital Multimeter, check that the resistance from the
PCT to all other conductive case components on the unit is <1Ω.
If any of the test measurements are not <1Ω then the root cause must be
identified and rectified before the unit can be returned to active service.