Cables
GFK-0356Q Chapter 10 Cables 10-43
10
Table 10-4. Wire List for 24-Pin Connectors
Pin Number Pair # Wire Color Code Pin Number Pair # Wire Color Code
A1 1 BLACK B1 7 BLUE
A2 1WHITE B2 7WHITE
A3 2 BROWN B3 8 VIOLET
A4 2WHITE B4 8WHITE
A5 3RED B5 9GRAY
A6 3WHITE B6 9WHITE
A7 4 ORANGE B7 10 BROWN
A8 4 WHITE B8 10 BLACK
A9 5 YELLOW B9 11 RED
A10 5 WHITE B10 11 BLACK
A11 6 GREEN B11 12 ORANGE
A12 6 WHITE B12 12 BLACK
CONNECTOR
3 2 1
12
12
3 2 1
B ROW
A ROW
NOTE
Each pair of wires should be tied together with heat
hi k
t
ubing for identification purposes. For example, a
ht
piece of heat shrink tubing should be placed around the
BLACK and WHITE wire pair (Pair #1) that connect to
Pins A1 and A2, etc.
Replacement/Obsolescence Information
This cable became obsolete and was replaced by cable IC693CBL315 (now obsolete also).
The only difference between these two cables is in the wire color coding.
When cable IC693CBL315 became obsolete, the replacement for these cables became
IC693CBL327 and IC693CBL328. Cables IC693CBL310/315 have straight connectors.
Cables IC693CBL327/328 have right angle connectors. The right angle connectors require
less depth in front of the PLC, so allow the use of a smaller enclosure in some applications.
Data sheets for cables IC693CBL315 and IC693CBL327/328 can be found in this chapter.
Connector Depth for Cable IC693CBL310
The following illustration shows the space required in front of the PLC when this cable is
connected to a module. The depth of the cabinet that the PLC is mounted in should allow for the
depth added by this connector.