Cables
GFK-0356Q Chapter 10 Cables 10-51
10
Table 10-9. Wire List for 24-Pin Connectors
Pin
Number
Pair # Wire Color Code Pin Number Pair # Wire Color Code
A1 1 BROWN B1 7 VIOLET
A2 1 BROWN/BLACK B2 7 VIOLET/BLACK
A3 2 RED B3 8 WHITE
A4 2 RED/BLACK B4 8 WHITE/BLACK
A5 3 ORANGE B5 9 GRAY
A6 3 ORANGE/BLACK B6 9 GRAY/BLACK
A7 4 YELLOW B7 10 PINK
A8 4 YELLOW/BLACK B8 10 PINK/BLACK
A9 5 DARK GREEN B9 11 LIGHT BLUE
A10 5 DARK GREEN/BLACK B10 11 LIGHT BLUE/BLACK
A11 6 DARK BLUE B11 12 LIGHT GREEN
A12 6 DARK BLUE/BLACK B12 12 LIGHT GREEN/BLACK
CONNECTOR
3 2 1
12
12
3 2 1
B ROW
A ROW
NOTE
Each wire pair has a solid color wire and that same color
wire with a black tracer. For example, Pair 1 has a solid
brown wire paired with a brown wire with a black tracer.
Replacement/Obsolescence Information
Cable IC693CBL315 (now obsolete also) replaced cable IC693CBL310 when that cable
became obsolete. The only difference between these two cables is in the wire color coding.
When cable IC693CBL315 became obsolete, the replacement for these cables became
IC693CBL327 and IC693CBL328. Cables IC693CBL310/315 have straight connectors.
Cables IC693CBL327/328 have right angle connectors. The right angle connectors require
less depth in front of the PLC, so allow the use of a smaller enclosure in some applications.
Connector Depth for IC693CBL315
The following illustration shows the space required in front of the PLC when this cable is
connected to a module. The depth of the cabinet that the PLC is mounted in should allow for the
depth added by this connector.