EasyManua.ls Logo

GE Series 90-30 PLC

GE Series 90-30 PLC
445 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C-10 Series 90-30 PLC Installation and Hardware Manual
August 2002 GFK-0356Q
C
*
150 OHMS
RD (A')
RD (B')
SD (A)
SD (B)
RTS (A)
RTS (B)
TERM
TERM
GND
RD (A')
RD (B')
SD (A)
SD (B)
RTS (A)
RTS (B)
TERM
TERM
GND
ISOLATED
REPEATER/
CONVERTER
(BRICK)
(USED AS A
CONVERTER)
25- PIN
MALE
15
14
16
17
13
12
22
23
7
PIN
25- PIN
FEMALE
SW
CTS
150 OHMS
*
**
ON THE CMM311, ONLY PORT 2 CAN SUPPORT RS-422/RS-485.
*
TERMINATE CONNECTION ON FIRST AND LAST DROPS ONLY: ON THE CMM, INSTALL JUMPER TO CONNECT INTERNAL
120 OHM RESISTOR. ON THE ISOLATED REPEATER/CONVERTER, INSTALL 150 OHM RESISTOR (SUPPLIED)
TO OTHER DEVICES
(MAXIMUM OF 8 DEVICES ON A MULTIDROP)
TERMINATE THE RD (B') SIGNAL ONLY AT END OF MULTIDROP CABLE
25- PIN
MALE
16
17
15
14
11
10
19
18
7
PIN
ISOLATED
REPEATER/
CONVERTER
(BRICK)
(USED AS A
REPEATER)
25- PIN
FEMALE
SW ON




















































































































J1 J2
J2 J1
SD (A)
SD (B)
RD (A')
RD (B')
CTS (A')
CTS (B')
TERM
TERM
GND
MAKE CONNECTIONS
INSIDE D-CONNECTORS
a44932
25- PIN
MALE
13
25
9
21
10
22
24
7
1
PIN
RD (A')
RD (B')
SD (A)
SD (B)
RTS (A)
RTS (B)
TERM
GND
SHLD





SHIELDED
TWISTED
PAIRS
25- PIN
FEMALE
SERIES 90
CMM
PORT
I
OR
2
**
ISOLATED
REPEATER/
CONVERTER
(BRICK)
25- PIN
FEMALE
SW
16
17
15
14
11
10
22
23
7
25- PIN
MALE
PIN
150 OHMS
*
*




























ALSO IT IS RECOMMENDED TO MAKE ANY
NECESSARY CONNECTIONS INSIDE THE
CABLE CONNECTOR TO BE MOUNTED ON
THE CMM. IT IS NOT RECOMMENDED TO
USE TERMINAL STRIPS OR OTHER TYPES
OF CONNECTORS ALONG THE LENGTH OF
THE TRANSMISSION LINE.
NOTE
WHEN WIRING RS-422 /485 MULTIDROP CABLES,
REFLECTIONS ON THE TRANSMISSION
LINE CAN BE REDUCED BY CONFIGURING THE
CABLE IN A DAISY CHAIN FASHION AS
SHOWN BELOW.
CMM SLAVE 1MASTER
CMM SLAVE 2CPU BUILT-IN PORT
























































ON
J2 J1
Figure C-9. Cable D; RS-422 Twisted Pair
CTS


























































































RD
SD
CTS
RTS
GND
DCD
DTR
SHLD
2
3
5
7
3
2
5
4
7
8
20
1
PIN
25- PIN
MALE
25- PIN
MALE
PIN
SD
RD
CTS
GND
SERIES 90
CMM
PORT
1
OR
2
25- PIN
FEMALE
a45239
ISOLATED
REPEATER/
CONVERTER
(BRICK)
25- PIN
FEMALE
J1
J2
SW
Figure C-10. Cable E; RS-232 Converter to CMM

Table of Contents

Related product manuals