56 ADV100 Functions description and parameters list
Analog inp x thr
x = 1, 2
Analog inp x <thr
Analog inp x thr
Analog inp x <thr
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.11 1622 Aninp1Xdeadband perc FLOAT 0.0 0.0 100.0 ERW FVS
14.26 1672 Aninp2Xdeadband perc FLOAT 0.0 0.0 100.0 ERW FVS
Deadband referring to the analog input signal. When the value on the input terminal is below the threshold dened
by the parameter, the output signal of the analog input block is forced to zero. Outside the deadband, the block out-
put varies linearly from zero to 100%.
AnInp Drive
AnInp Terminal
100%
-100%
10V
-10V
100%
-100%
Par.1522=50%
Par.1522=50%
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.12 1624 Aninp1Xaltvalue cnt INT16 16/32BIT 0 -16384 16384 ERW FVS
14.27 1674 Aninp2Xaltvalue cnt INT16 16/32BIT 0 -16384 16384 ERW FVS
Setting of a xed alternative value for the relative analog input, which can be selected via a command enabled by a
digital input programmed with theAninpxXaltselsrc parameter.
Menu PAR Description UM Type FB BIT Def Min Max Acc Mod
14.13 1626 Aninp1Xsignsrc LINK 16 6000 0 16384 ERW FVS
14.28 1676 Aninp2Xsignsrc LINK 16 6000 0 16384 ERW FVS
Selection of the origin (source) of the signal to be assigned to the relative digital input of the expansion card for
selecting the direction of rotation of the motor. The functions that can be associated with the digital outputs are listed
in the “L_DIGSEL2” selection list.