Installation
Iss. a Translation of the original version
2024/01/05
Doc. Ref. : SOUND2.940.001
Niveau de remplissage
Filling level
Point de calibration 2
Calibration point 2
Point de calibration 1
Calibration point 1
Valeur du spectre de puissance dans la zone de
mesure
Value of the power spectrum in the
measurement zone
1. Check the default values in the “Calibration” menu.
The 1
st
calibration point is carried out empty, in order to measure the sound when the mill is empty.
Characteristics
Values
Calib. N° Point
1
Filling Level
10%
Power Max
xxxxxxxx
Gain
30
Calibration Status
0
Calibration Mode
Automatic
Start
Stop
The “Power Max” must be other than 0 and vary moderately around a fixed value.
2. Press “Start to set the 1
st
calibration point. The controller goes back to the main screen and the text
“Calibration in progress” flashes at the top of the display.
3. Wait for a few seconds. When calibration is complete, the text Ready” is displayed and the Filling (or
Noise) level is indicated on the screen
Figure 27: “Calibration in progress” menu