114
SETTING THE ENABLE OR REDUCTION TIMES
On the HDG Pelletronic control unit, you can set the enable or
reduction times for the heating system. For each day of the week you
can set a maximum of four different enable times or reduction times.
At the set reduction times, the boiler supply temperature is reduced.
Select the required level as follows:
1. Press the Enter button.
✓ The customer level is shown on the display.
2. Using the Down button, select the parameter group 2.
3. Press the Enter button.
4. Press the Down button repeatedly until Par. 2-10 or 2-11 in
the main menu is shown on the display.
✓ Either Par 2-10 or 2-11 are shown in the display.
5. Press the Enter button.
✓ The cursor flashes underneath the first day of the week Mon.
✓ The value displayed can be changed.
6. Press the Plus or Minus button.
✓ The weekday is hidden or displayed.
7. Press the Down button.
✓ The cursor flashes underneath the next weekday.
8. Hide the days where no enable or reduction times are to be
entered, as described in step 4.
9. Press the Down button repeatedly until the cursor flashes under
the first time field ON 00:00.
✓ The cursor will flash underneath the first time field.
10.Press the Plus or Minus button.
✓ The value of the parameter is increased or decreased in
increments of 15 minutes.
11.Configure the reduction times as described under step 8.
✓ The reduction times have been set.
12.Press the Enter button.
✓ The set reduction times have been confirmed.