ANNUAL INSPECTION In Germany, regular annual inspections must be carried out in
accordance with the requirements of the federal pollution limits
(1.BImschV).
BEFORE THE MEASUREMENT
1. Clean the heating system.
✎ See chapter “7 Cleaning and maintaining the heating system”,
section “7.1 Cleaning and maintenance schedule”.
2. Check that the lambda sensor is securely mounted and tighten it
if necessary.
✎ See chapter “7 Cleaning and maintaining the heating system”,
section “7.2 Procedure”.
Once the chimney sweep is ready for the measurement:
3. Press the Mode button repeatedly until the CHIMNEY SWEEP
TEST symbol flashes.
✓ The operating mode CHIMNEY SWEEP TEST has been
preselected.
4. Press the Enter button.
✓ The operating mode CHIMNEY SWEEP TEST has been confirmed.
✓ The CHIMNEY SWEEP TEST symbol lights up.
✓ The heating system switches to CHIMNEY SWEEP TEST mode.
✓ If the HDG Hydronic equipment is connected, all of the loads will
automatically be activated to maximise the heat transfer.
✓ The display will show No test yet.
DURING THE MEASUREMENT
Please observe the following when carrying out the chimney sweep
test:
• Make sure that there is sufficient material in the pellet bunker to
avoid having to interrupt the measurement for reloading.
• No fault should be present in the system.
When starting the test, the boiler temperature should not exceed
75 °C. If there is an accumulator, its temperature should not exceed
60 °C. Ensure there is sufficient heating demand placed on the
heating circuit.
Having the measurement repeated by the combustion engineer or
by HDG specialists will incur charges.