8.3 Configuring emergency operation
REQUIREMENTS If the remedy to your problem is listed in Table 8/1 - Faults as
“Configure emergency operation”, activate emergency operation on
the HDG Pelletronic as follows.
P
ROCEDURE 1. Press the Enter button.
✓ The customer level is shown on the display.
2. Use the Down button to change to Par. 1-04.
✓ The display will change to Par. 1-04.
3. Press the Enter button.
✓ The cursor will flash underneath the parameter 0.
✓ The value displayed can be changed.
4. Press the Plus button.
✓ The value of the parameter is increased to 1.
5. Press the Enter button.
✓ The changed value is confirmed.
✓ Emergency operation has been configured.
6. Press the Menu button twice.
✓ The standard display of i-01 is shown.
F
URTHER MEASURES Have the fault fixed by an authorised heating engineer.
F202 CAN data
transmission
write fault
• Data transmission to
Hydronic is faulty
• Call HDG service
F999 Fault/error
was acknowledged
• Entered in the fault buffer
when a fault is acknowledged
• No action required
No. Fault Cause Remedy
Table 8/1 - Faults (continuation)