8 Troubleshooting – Possible faults
164
F091 Indoor
thermostat unit
CCT6
Short circuit
Short circuit in indoor
thermostat unit
Incorrect terminal connection
Have the fault fixed by a
qualified electrician
F092 Upper boiler
temperature
sensor 2
Open circuit
Sensor not connected
Sensor is faulty
Have the fault fixed by a
qualified electrician
F093 Upper boiler
temperature
sensor 2
Short circuit
Short circuit in sensor or in
cable
Both sensor connections
joined in a single terminal
Have the fault fixed by a
qualified electrician
F100 Fault buffer
was deleted
Displayed when the fault
buffer is deleted
No action required
F101 Restart (power
ON)
Entered in the fault buffer
when the control unit is
restarted
No action required
F103 Heating circuit
module 1
ADC fault
Analogue to digital converter
is faulty
New heating circuit control
F104 Heating circuit
module 1
Fault in 0-
throughput
Speed-controlled output is
faulty
New heating circuit control
F170 No connection to
GSM module
GSM module can not be
signalled by the central unit
Cable connection is faulty
GSM module without voltage
or faulty
Have the fault fixed by a
qualified electrician
F171 GSM transmitter
error or
unavailable
network or SIM
card
No GSM reception, no SIM
card in GSM module
No credit balance on
telephone connection
SIM card expired (e.g. if SIM
card has not been reloaded
for over a year)
Check reception in info page
32
Query credit balance
Load SIM card
Call HDG service
F200 CAN data
transmission
incorrect ID
Data transmission to
Hydronic is faulty
Call HDG service
F201 CAN data
transmission
read fault
Data transmission to
Hydronic is faulty
Call HDG service
No. Fault Cause Remedy
Table 8/1 - Faults (continuation)