8 Troubleshooting – Procedure
157
8 Troubleshooting
If a fault occurs in the heating system, all of the operating mode
symbols flash and the fault is shown in the display. Faults can be fixed
as follows.
8.1 Procedure
1. Look for the displayed fault's cause and remedy in Table 8/1 -
Faults.
2. Fix the fault, or have it fixed.
3. Acknowledge the fault with the Enter button.
4. For faults which affect safety, switch the main switch off and back
on again after waiting several seconds.
The symbol for the current operating mode lights up.
The fault message is no longer shown in the display.
The fault is fixed.
8.2 Possible faults
Enter
No. Fault Cause Remedy
Mains switch is
turned on but
the indicator in
the switch does
not light up
Circuit breaker of the mains
supply is turned off
Mains supply is not
connected
Microfuse underneath the
mains switch is faulty
Switch on the circuit breaker
of the mains supply
Have the mains supply
connected by a qualified
electrician
Exchange the microfuse
F001 Safety
thermostat
Excessive boiler temperature
or the wiring is faulty
Fuse F2 (on I/O circuit board)
faulty
Have the fault fixed by a
qualified electrician
Table 8/1 - Faults