143
20 OIL-FIRED BOILER
21 COMBINATION HEATING
PUMP
No. Display Description
20-01 Oil-fired boiler
Oil-fired boiler temp.
Minimum
( 40) 40°
• The minimum temperature of the oil-fired boiler
Set the minimum temperature of the oil-fired boiler.
(10 - 100 °C)
20-02 Oil-fired boiler
Oil-fired boiler temp.
Maximum
( 70) 70°
• Maximum temperature of the oil-fired boiler
Set the maximum temperature of the oil-fired boiler.
(10 - 100 °C)
20-03 Oil-fired boiler
Oil-fired boiler temp.
Increase
( 5) 5°
• To increase the temperature of the oil-fired boiler
Set the increase in temperature of the oil-fired boiler.
(10 - 100 °C)
20-04 Oil-fired boiler
Hysteresis of oil-
fired boiler
( 5) 5°
• Hysteresis of the oil-fired boiler
Set the difference between the oil-fired boiler
temperatures for switching on and off.
(10 - 100)
20-05 Oil-fired boiler
Oil-fired boiler
enable time
(30) 30 m
• Enable time for the oil-fired boiler
The oil-fired boiler is activated if the highest load enable
temperature is not met within the preset time.
(0 - 360 m)
Table 6/16 - Service level / 20 Oil-fired boiler
No. Display Description
21-01 Combination heating
pump
Enable temperature
Combination buffer/HW
heating pump
( 50) 50°
• Enable temperature for the heating pump
If the preset temperature is not met, the combination
buffer can be heated by the oil-fired boiler.
(20 - 100 °C)
Table 6/17 - Service level / 21 Combination heating pump