8.8.2.8 Heat Pump conguration
Water pump conguration:
Congure the water pump of the
heat pump.
See detailed information in the
next page.
Night shift:
Reduces compressor load in order
to reduce environmental noise,
preferably at night.
See detailed information in the next
page.
Minimum ON time: In order to reduce a possible
compressor damage, demand ON cycles can be
reduced by determining the time that must pass before
accepting new Demand OFF.
Minimum OFF time: In order to reduce a possible
compressor damage, demand OFF cycles can be
reduced by determining the time that must pass before
accepting new Demand ON.
Seizure protection: The pump seizure protection
function prevents sticking of components due
to long periods of inactivity, by running the
components during a short period every week.
Mixing valves and pumps are fully opened and
then fully closed (time depends on Mixing valve
Run Time Factor).
Outdoor average temperature:
OTC average is used to neutralise the effect of
occasional temperature variations.
The average value of outdoor temperature sampled
over a selected period (between 1 and 24 hours) is
used for the calculation of weather-dependent set point
temperature.