ENGLISH
9.13.4.2 Water settings conguration
This menu is only visible for a room thermostat if the controller is not controlling the unit.
Select the desired area to apply the water settings conguration:
Space Heating or Space Cooling water settings
∆θ (Vertex offset):
To modify the curve vertex for Circuit 1 or Circuit
2 (only for heating mode).
• Only when water calculation mode is
Gradient or Points (setting in Main device).
• Range: -10 ~ 10
• Circuit 1 or Circuit 2 must be ON to congure
this setting.
Fixed temperature:
Selection of the temperature for Circuit 1 or Circuit 2
(heating or cooling mode).
• Only when water calculation mode is Fix (setting
in Main device).
• Circuit 1 or Circuit 2 must be ON to congure this
setting.
Curve:
Selection of the gradient curve for Circuit 1
or Circuit 2 (only for heating mode).
• Only when water calculation mode is
Gradient (setting in Main device).
• Range: 0.2 ~ 2.2
• Circuit 1 or Circuit 2 must be ON to
congure this setting.
Hot Water Tank or Swimming pool water settings
Setting temperature:
Selection of the temperature for DHW or Swimming Pool.
• Hot water tank or Swimming pool must be ON to congure this setting
• Range:
- DHW: 30 ºC ~Max. setting temperature
- Swimming pool: 24 ~33 ºC
UNIT CONTROLLER (PC-ARFH2E)
PMML0575 rev.2 - 03/2022
211