11.13.3.2 Water settings conguration
This menu is only visible for a room thermostat if the controller is not controlling the unit.
Select the desired area to apply the water settings conguration:
Space Heating or Space Cooling water settings
θ (Vertex offset):
To modify the curve vertex for Circuit 1 or
Circuit 2 (only for heating mode).
Only when water calculation mode is
Gradient or Points (setting in Main device).
Range: -10 ~ 10
Circuit 1 or Circuit 2 must be ON to
congure this setting.
Fixed temperature:
Selection of the temperature for Circuit 1 or Circuit
2 (heating or cooling mode).
Only when water calculation mode is Fix
(setting in Main device).
Circuit 1 or Circuit 2 must be ON to congure
this setting.
Curve:
Selection of the gradient curve for Circuit 1 or
Circuit 2 (only for heating mode).
Only when water calculation mode is
Gradient (setting in Main device).
Range: 0.2 ~ 2.2
Circuit 1 or Circuit 2 must be ON to
congure this setting.
Hot Water Tank or Swimming pool water settings
Setting temperature:
Selection of the temperature for DHW or Swimming Pool.
Hot water tank or Swimming pool must be ON to congure
this setting.
Range:
- DHW: 30ºC ~ Max. setting temperature
- Swimming pool: 24 ~33ºC
YUTAKI CASCADE CONTROLLER ATW-YCC-03
PMML0575 rev.2 - 03/2022