9.13.4.9 Optional functions conguration
This menu allows to congure the optional functions for system, space heating or space cooling, DHW and Emergency operation.
Hot water tank:
Congure the optional functions for the DHW. See
detailed information below.
Emergency operation:
Enable or disable emergency operation for space
heating or DHW. See detailed information below.
Energy conguration:
Setup of power consumption readings. See
detailed information below.
Hydraulic separator:
Enable or disable a Hydraulic separator
or a buffer tank. See detailed information
below.
Heating Auto On/Off:
To stop automatically stop heating operation when
the daily average outdoor temperature of the
previous day is higher than the dened Switch-
OFF temperature. See detailed information below.
Auto Heat/Cool:
Allows to set automatic switch over to heating and
cooling operation using the same daily average
outdoor temperature of the previous day as in
Heating auto ON/OFF.
Smart function:
To block or limit the heat pump or
increase demand due to electricity
availability. See detailed information on
Smart function chapter.
1 / 2
2 / 2
Hydraulic separator
Hydraulic separator status:
Enable if there is a Hydraulic separator or a
buffer tank installed. Check that WP3 is set
in output 2 (see section “9.13.4.10 Inputs,
Outputs and Sensors conguration”).
DWH Tank position:
This selection option is not available for
YUTAKI S COMBI since DHW tank is located
before buffer tank in any case.
Pre: DHW tank and the 3 way valve are
located between Heater Plate exchanger and
buffer tank.
Post: DHW tank and the 3 way valve are
located after buffer tank.
UNIT CONTROLLER (PC-ARFH2E)
PMML0575 rev.2 - 03/2022
222