4.4 SPLIT SYSTEM - INDOOR UNIT
4.4.1 YUTAKI S
RWM-(2.0-10.0)(N/R)1E
Model Power supply
Applicable voltage
Operation mode
RNC
(A)
IPT
(kW)
MC
(A)
Max.
IPT
(kW)
U max.
(V)
U min.
(V)
RWM-2.0R1E
1~ 230V 50Hz 253 207
Without electric heater 0.5 0.06 0.63 0.06
With electric heater 13.7 3.06 13.7 3.06
With DHW tank heater 13.7 3.06 13.7 3.06
With electric and DHW tank heaters 26.7 6.06 26.7 6.06
3N~ 400V 50Hz 440 360
Without electric heater 0.5 0.06 0.6 0.06
With electric heater 4.8 3.06 5.0 3.06
With DHW tank heater 4.5 3.06 13.7 3.06
With electric and DHW tank heaters 8.9 6.06 18.0 6.06
RWM-(2.5-3.0)R1E
1~ 230V 50Hz 253 207
Without electric heater 0.6 0.06 0.6 0.06
With electric heater 13.7 3.06 13.7 3.06
With DHW tank heater 13.7 3.06 13.7 3.06
With electric and DHW tank heaters 26.7 6.06 26.7 6.06
3N~ 400V 50Hz 440 360
Without electric heater 0.6 0.06 0.6 0.06
With electric heater 4.8 3.06 5.0 3.06
With DHW tank heater 4.5 3.06 13.7 3.06
With electric and DHW tank heaters 8.9 6.06 18.0 6.06
RWM-(4.0-6.0)N1E
1~ 230V 50Hz 253 207
Without electric heater 0.6 0.08 0.7 0.08
With electric heater 26.7 6.08 26.7 6.08
With DHW tank heater 13.7 3.08 13.7 3.08
With electric and DHW tank heaters 39.8 9.08 39.8 9.08
3N~ 400V 50Hz 440 360
Without electric heater 0.6 0.08 0.7 0.08
With DHW tank heater 9.1 6.08 9.3 6.08
With DHW tank heater 4.5 3.08 13.7 3.08
With electric and DHW tank heaters 13.3 9.08 22.4 9.08
RWM-(8.0-10.0)N1E 3N~ 400V 50Hz 440 360
Without electric heater 0.3 0.08 0.7 0.14
With DHW tank heater 13.1 9.08 13.7 9.14
With DHW tank heater 4.5 3.08 13.7 3.14
With electric and DHW tank heaters 17.5 12.08 26.7 12.14
? NOTE
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
ELECTRICAL DATA
PMML0575 rev.2 - 03/2022
26