Water pump conguration
Operation mode:
ΔT: To control the pump speed to guarantee
the ΔT between Two and Twi.
Fix: The water pump works at the specied
speed % at the space speed menu.
Space speed:
Selection of the % for the pump speed when x
mode is selected.
DHW speed:
Selection of the % for the pump speed when
using DHW.
Swimming pool speed:
Selection of the % for the pump speed
when using Swimming pool.
Minimum OFF Time:
Minimum time of the water pump OFF.
Only when Economic mode is active (DSW)
Minimum ON Time:
Minimum time of the water pump ON.
Only when Economic mode is active (DSW)
Pumps during DHW:
This option allows to stop Water Pumps during
DHW operation. Water pumps that are allowed
to stop are the ones that are not directly involved
to DHW heating-up procedure. This is WP2 and
WP3 depending on the hydraulic conguration.
Overrun Time:
Added operation time of water pump
after Demand OFF.
Stop conditions:
Standard
Thermo OFF: The water pump stops
after Thermo OFF. (DSW5 pin 4 ON).
Pump Setup:
This option allows user to select hydraulic
conguration of the system when hydraulic
separator is used.
Standard: WP2 is connected after WP3 by means an
hydraulic separator or directly by means Hitachi mixing kit
accessory. Whenever WP2 is switched ON, WP3 is also
switched ON in order to transfer heat to C2.
Parallel: WP2 is directly connected to the buffer tank in
parallel with WP3. Operation of WP3 is independent of the
operation of WP2. When this conguration is used, Hitachi
mixing kit accessory cannot be used.
Option available only when there is Hydraulic separator
congured.
2 / 2
1 / 2
Night Shift
Starting time of Nigh Shift operation
Ratio of reduction in heat pump capacity
Status of activation of Night Shift (reduction of compressor load in
order to reduce operation noise during the night hours).
Ending time of Night Shift operation
UNIT CONTROLLER (PC-ARFH2E)
PMML0575 rev.2 - 03/2022
220

Table of Contents

Other manuals for Hitachi YUTAKI RWM-2R1E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi YUTAKI RWM-2R1E and is the answer not in the manual?

Hitachi YUTAKI RWM-2R1E Specifications

General IconGeneral
BrandHitachi
ModelYUTAKI RWM-2R1E
CategoryAir Conditioner
LanguageEnglish

Related product manuals