Monobloc system - R410A YUTAKI M
Model
Power supply Operation mode
Max.
current
(A)
Power supply
cables
Transmitting
cables
Actuator
cables
EN60335-1 EN60335-1 EN60335-1
RASM-4VNE
1~ 230V 50Hz
Without DHW tank heater 31 2 x 6.0 mm² + GND
2 x 0.75 mm
2
(Shielded
cable)
2 x 0.75 mm
2
+ GND
With DHW tank heater 43 2 x 10.0 mm² + GND
RASM-5VNE
Without DHW tank heater 31 2 x 6.0 mm² + GND
With DHW tank heater 43 2 x 10.0 mm² + GND
RASM-6VNE
Without DHW tank heater 31 2 x 6.0 mm² + GND
With DHW tank heater 43 2 x 10.0 mm² + GND
RASM-4NE
3N~ 400V 50Hz
Without DHW tank heater 14 4 x 4.0 mm² + GND
With DHW tank heater 27 4 x 6.0 mm² + GND
RASM-5NE
Without DHW tank heater 14 4 x 4.0 mm² + GND
With DHW tank heater 27 4 x 6.0 mm² + GND
RASM-6NE
Without DHW tank heater 16 4 x 6.0 mm² + GND
With DHW tank heater 29 4 x 10.0 mm² + GND
? NOTE
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
Monobloc system - R32 YUTAKI M
Model Power supply Operation mode
Max.
current
(A)
Power supply
cables
Transmitting
cables
Actuator
cables
EN60335-1 EN60335-1 EN60335-1
RASM-2VRE
1~ 230V 50Hz
Without DHW tank heater 11 2 x 2.5 mm² + GND
2 x 0.75 mm
2
(Shielded
cable)
2 x 0.75 mm
2
+
GND
With DHW tank heater 23 2 x 6.0 mm² + GND
RASM-3VRE
Without DHW tank heater 16.0 2 x 4.0 mm² + GND
With DHW tank heater 29 2 x 6.0 mm² + GND
? NOTE
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
ELECTRICAL AND CONTROL SETTINGS
PMML0575 rev.2 - 03/2022
79

Table of Contents