Monobloc system - R410A YUTAKI M
Model Power supply
Applicable voltage
Operation mode
MC
(A)
CB
(A)
ELB
(nº of poles/A/mA)
U max. (V) U min. (V)
RASM-4VNE
1~ 230V 50Hz 253 207
Without DHW tank heater 31 32 2/40/30
With DHW tank heater 43 50 2/63/30
RASM-5VNE
Without DHW tank heater 31 32 2/40/30
With DHW tank heater 43 50 2/63/30
RASM-6VNE
Without DHW tank heater 31 32 2/40/30
With DHW tank heater 43 50 2/63/30
RASM-4NE
3N~ 400V 50Hz 440 360
Without DHW tank heater 14 20
4/40/30
With DHW tank heater 27 30
RASM-5NE
Without DHW tank heater 14 20
With DHW tank heater 27 30
RASM-6NE
Without DHW tank heater 16 20
With DHW tank heater 29 40 4/63/30
? NOTE
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
Monobloc system - R32 YUTAKI M
Model Power supply
Applicable voltage
Operation mode
MC
(A)
CB
(A)
ELB
(nº of poles/A/mA)
U max. (V) U min. (V)
RASM-2VRE
1~ 230V 50Hz 253 207
Without DHW tank heater 11 16
2/40/30
With DHW tank heater 23 32
RASM-3VRE
Without DHW tank heater 16 20
With DHW tank heater 29 32
? NOTE
The data corresponding to DHW tank heater is calculated in combination with the domestic hot water tank accessory “DHWT-(200/300)S-3.0H2E”.
ELECTRICAL AND CONTROL SETTINGS
PMML0575 rev.2 - 03/2022