Electric heater control functions
SMGB0066 rev.0 - 12/2009
This function can be disabled by setting parameter P32=OFF.
P32  Supply-Return Difference Limit (default 3K)
A high value will prevent the electric heater switching on until a large temperature difference is seen by the System 
Controller.Withalowvalueorwiththefunctiondisabled,theelectricheatermaystartmoreoften,forexampleduring
defrost cycles.
note
This check is ignored if the Heat Pump is switched off or has an internal fault. -
 
Itisimportantwithmono-energeticsystemsthattheHeatpumpshouldrsttrytosatisfytheheatingdemandbyitself.
For this reason an electric heater waiting time applies. This means that when the heatpump cannot meet the heating 
demand,thentheelectricheaterisswitchedononlyafterthewaitingtimehaselapsed.
The waiting time starts:
Whentheheatpumpisswitchedon,or
When the electric heater switches off (but only also when the Supply Setpoint SSUP < heat pump maximum temperature 
– heat pump sensor offset).
Thismeansthatwhentheheatpumpshouldnormallybeabletomeettheheatingdemandonitsown,theelectricheater
waitingtimeapplies,butwhenthesupplysetpointissohighthattheheatpumpcannotmeettheheatingdemandonits
own,thewaitingtimedoesnotapply.
P19   Waiting Time for Electric Heater (default 30min.)
AhighervalueofP19willreducethenumberoftimesthattheelectricheaterisusedatlowersupplysetpoints,butthe
desiredsupplytemperaturemaynotbereachedquicklyifthereisahighheatingload(slowerresponse).Conversely,a
lowervalueofP19willincreasethenumberoftimestheelectricheaterisusedatlowersupplysetpoints,butensurethat
the desired supply temperature is reached more quickly (better response).
 
The return high limit check is used to help ensure that the heat pump operates as much as possible even when higher 
supplytemperaturesarerequired,thusemphasisingenergyeconomyoperation.Theelectricheaterisdisabledwhenthe
return water temperature (TRET) rises above the maximum heat pump outlet temperature minus the return limit offset 
(P33). A +/-0.5K control differential applies.
TRET > Heat Pump maximum supply temperature – P33 + 0.5K   Electric Heater disabled
TRET < Heat Pump maximum supply temperature – P33 - 0.5K  Electric Heater enabled
Sincetheelectricheaterisswitchedoffthenthereturntemperaturerisestoohigh,theeffectwillbethatinsomesystem
conditionsitwillnotbepossibletoreach65°Csupplytemperature.Ifitisimportanttoallow65°Coperation,thenthe
parametercanbereducedorsettoOFF,buttheresultisthatinsomesituationstheelectricheaterwilloperateonits
own and the heat pump will not be used. This will cause higher energy costs.