Controller pack
Service Manual
118
Systemcongurations
SMGB0066 rev.0 - 12/2009
TERMINAL 
BLOCK C
TERMINAL 
BLOCK C
TERMINAL 
BLOCK C
T MIX
T DHW
T RET
T SUP
T EXT
10
9
5
4
3
2
1
15
14
¡
The Heat Pump is sized to provide 100% of the heating requirements on the coldest day of the year. Used in new builds or in 
boiler-replacement applications.
• DirectOTCControlledHeatingLoop
• OptionalDHWstoragewithdivertingvalveorpump
Thiscongurationissuitableforlow-temperatureradiatorsandunderoorheatingsystems.
 
• SetinstallerparameterCONFtovalue1
• SetinstallerparameterP1to0(noDHW),1(DHWvalve)or2(DHWpump)
• SetP4(OTCheatingcurve)accordingtobuilding/system
 
•
 SetinstallerparameterP2to0(nosecondarypump),1
(secondarypump9,ifbuffertankorhydraulicseparatorisused
•
 DHW setpoint and control parameters
•
 Minimum and maximum supply temperatures
•
 Room temperature compensation
•
 Frost Protection parameters
•
 Summer switch-off setting
•
 Tariff/Timerinputconguration
-  Heat Pump
-  Optional DHW valve/ pump
-  Optional secondary pump
-  Optional DHW electric heater