EasyManua.ls Logo

Hitachi YUTAKI Series - Principle of Bi-Valent or Mono-Energetic Operation

Hitachi YUTAKI Series
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Controller pack
Service Manual
76
Systemconguration,settingsandcontrolsystem
SMGB0066 rev.0 - 12/2009

TheSystemControllercanbeusedinasystemwhichhasaDHWstoragetank,witheitheradivertingvalveorpump.
IfthesystemhasaseparateDHWpump,thenahydraulicseparatororbuffertankhastobeusedtoensureproper
hydraulic balancing of the system.
The DHW system type is selected by an installer parameter (P1)

WhenahydraulicseparatororbuffertankisusedinCONF1&2,thesystemwillcontainasecondarypumponthe
distribution side of the separator/buffer. In this case it is necessary to set installer parameter P2 to 1.
Inbi-valentsystems(CONF3,4,5)ahydraulicseparatororbuffertankisalwaysneeded.
 

Bi-valent and mono-energetic systems use an auxiliary heat source (boiler or electric heater respectively) in addition to
the heat pump.
Athigheroutdoortemperatures,theheatpumpcanprovidealltheheatingrequirementsofthesystem,anditisnot
necessarytoswitchontheauxiliaryheatsource.Howeveratloweroutdoortemperatures,theelectricheaterorboileris
used to provide the increased heating demand. The changeover point for bi-valent or mono-energetic operation is called
the balance point. A +/-0.5K control differential is applied to the switching between the operating modes.
Outdoortemperature(TEXT)>BalancePoint(BP)+0.5K,theboilerorelectricheaterisnotused.(Exceptionisthatthe
boiler can be used for DHW loading.)
Outdoortemperature(TEXT)<Balancepoint(BP)-0.5K,thesystemcontrollerdetermineswhethertoswitchontheboiler
or electric heater depending on the heating requirements. Refer to the sections on Boiler Control and Electric Heater
Control for more details.

P15 Maximum Outdoor Temperature for Boiler/Electric Heater Operation = Balance Point (BP) (default 0°C)
P14 MinimumOutdoorTemperatureforHeatPumpOperation(CONF3,4,5only)(default-20°C)
note
Parameter P15 can be set to OFF, in which case the boiler or electric heater is allowed to operate at all outdoor -
temperatures
Parameter P14 can be set to OFF, in which case the heat pump is allowed to operate at all outdoor -
temperatures.

CONF 2 Mono-Energetic Systems -
The electric heater is used to “top-up” the energy required for the system. The System Controller tries to ensure that
theheatpumpisalwaysrunningwhentheelectricheaterisused,buttheremaybesomecircumstanceswherethe
electric heater is providing all the energy for the heating system.
Heating Zone
Heat Pump Capacity (kW)
Heat Demand (kW)
Electric Heater
Heat Pump
Only
Heat Pump
20ºC P15 -20ºC Outside Temp
Heat Pump operates
on it’s own down to the
balance point (installer
parameter )
Heat Pump plus
Electric Heater
operate together

Table of Contents

Other manuals for Hitachi YUTAKI Series

Related product manuals