Controller pack
Service Manual
86
DHW control functions
SMGB0066 rev.0 - 12/2009
DHW diverting valve system DHW pumped system
TheDHWfunctionhaspriorityovertheHeatingCircuit,whichmeansthatwhentheDHWstoragetankisbeingloaded,
the heating circuit will be switched off.
TheDHWfunctionwillbeblocked(temporarilydisabled)whentheTariff/TimerinputisconguredforDHWandtheinput
isopencircuit(oralternativelyshortcircuitasdenedbyparameter–see“DHWTimeProgram”).
P1 System DHW Choice (default 0)
P1=0   No DHW function -
P1=1  System with DHW diverting valve -
P1=2  System with DHW pump -
 
WhenDHWcontrolisenabled,thesystemcontrollerheatstheDHWtanktemperaturetotheDHWsetpoint(P10).When
theDHWtemperaturedropsbelowtheDHWsetpointminustheDHWdifferential(P11),thisfunctionswitchesonthe
DHWPumporopenstheDHWvalve,andsetsasupplysetpointequaltoDHWsetpoint+DHWsupplyoffset(P12).The
DHW loading is complete when the DHW temperature rises above the DHW setpoint.
Supply Setpoint for DHW loading = DHW setpoint + DHW Supply Offset (P12)
DSET = DHW setpoint (P10)
SDHW = Supply Setpoint for DHW loading.
TDHW = DHW tank temperature
 DHW loading starts (power-on or DHW timer signal) 
Supply water temperature set to P10+P12
(*)
 DHW tank temperature (TDHW) rises above P10 
DHW loading stops 
Supply water temperature is determined by heating circuit 
requirements.
 DHW tank temperature (TDHW) falls below P10 - P11 
DHW loading starts 
Supply water temperature set to valve P10+P12
(*)
note
The Heat Pump outlet temperature setpoint will be equal  -
to the Supply Water Temperature Setpoint + P31 (Heat 
Pump supply offset) to account for pipe losses. The Heat 
Pump outlet temperature setpoint is always limited to 55º 
C or 50º C depending on the outside temperature.