127
System testing
SMGB0066 rev.0 - 12/2009
Controller pack
Service Manual
4
The table below shows the values that are available to be viewed during Normal Operation mode. These can be shown by
pressing the
button
Sensor
Temperatures
TEXT Outdoor temperature °C 12345
TSUP Supply water temperature °C 12345
TMIX Zone1: Mixed supply temperature °C ---45
TRET Return temperature °C 12345
TDHW DHW temperature °C 123-5
TR1 Room temperature °C 12345
V Mixing valve position - ---45
FAUL Fault status - 12345
Controller Setpoints
SSUP Overall system supply setpoint °C 12345
S1 Zone1: supply setpoint °C 12345
SR1 Zone1: room setpoint °C 12345
S2 Zone2: supply setpoint °C 12345
DSET DHW setpoint °C 123-5
SDHW DHW supply setpoint °C 123-5
note
Operational data shown depends on the system conguration (CONF) setting. -
Zone 1 is the heating loop controlled by the System Controller. -
Zone 2 is the heating loop controlled by the Extension Controller. -
This feature allows the status of the outputs to be changed in order to test the electrical connections.
ToenterOutputDisplaymodefromNormalOperatingmode,pressthe
SEL
and
SET
buttons together for at least one
second.Thedisplaywillshow“HPS”toindicatethatthecontrollerisinOutputDisplaymodeandshowstherstoutput
“HPS” and its current status.
Use the 1.
and buttons to move up or down the output list according to the table.
Tochangeanoutput,usethe2.
SET
buttontoenterOutputSettingmode.Thevalueoftheoutputwillashtoshowthatit
cannowbechanged.Tochangetheoutputvalue,usethe
and buttons.
Tosavetheoutputsetting,pressthe3.
SET
button.Theashingwillstoptoshowthevaluehasbeensaved,andtheletter
F (Fixed) will appear to show that the output is being overridden. Note that the value must be saved before it takes effect.
Instead,tocancelthechange,andretainthepreviouslystoredvalue,pressthe
SEL
button.
Tocancelthemanualoverrideofanoutput,entertheOutputSettingmodeandthenpress
and together for one
second. The “F” disappears from the display to show that the output is no longer overridden.
Atanytime,pressingthe button will return the display to Normal Operation mode.
Please refer to the electrical wiring connections to identify which relays should be connected to which output for a particular
systemconguration