Controller pack
Service Manual
128
Expanding the system
SMGB0066 rev.0 - 12/2009
ID Output Min Max CONF
HPS Heat Pump setting (mA) 2 20 12345
HP Heat Pump remote on/off 0 1 12345
PO2 Secondary pump (not displayed if P2=0) 0 1 12345
DHWV DHW valve/pump (not shown if P1=0) 0 1 123-5
EHS1 Electric heater output 1 0 1 -2---
EHS2 Electric heater output 2 0 1 -2---
DHWE DHW electric heater enable (not shown if P1=0) 0 1 12---
PO1 Boiler pump 0 1 --34
BLR Boiler on/off 0 1 --345
V Mixing valve position (%) 0 99 ---45
Operational data shown depends on the system conguration (CONF) setting.
The system controller is designed so that it can be expanded when necessary to control heating systems with an additional
mixedheatingzone.Theextensioncontrollerwillcontrolamixingcircuit,consistingofamixingvalveandpumpasshown
below.Itispossibletouseoneroomunitfortheentiresystem,orhaveoneroomunitineachheatingzonewithseparate
time programmes.
Installation instructions are included with the extension controller.