Boiler control functions
SMGB0066 rev.0 - 12/2009
Controller pack
Service Manual
4
Inordertopreventinefcientshort-cyclingoftheboiler,thisfunctionpreventstheboilerfromswitchingonorswitchingoff
until either the boiler minimum off time or boiler minimum on time,respectively,haselapsed.
P17 Boiler minimum ON time (default 2 min.)
P18 Boiler minimum OFF time (default 5 min.)
HighvaluesofminimumONandOFFtimesmaycauselargeuctuationsinwatertemperatureandshouldusuallybe
avoided.
note
If the boiler is disabled, rather than off due to normal control (load=0%), then the boiler minimum ON time does -
not apply
Itisimportantwithbi-valentsystemsthattheHeatpumpshouldrsttrytosatisfytheheatingdemandbyitself.Forthis
reasonaboilerwaitingtimeapplies.Thismeansthatwhentheheatpumpcannotmeettheheatingdemand,thenthe
boiler is switched on only after the waiting time has elapsed.
The waiting time starts:
Whentheheatpumpisswitchedon,or -
When the boiler switches off (but only also when the Supply Setpoint SSUP < heat pump maximum temperature – -
heat pump sensor offset).
Thismeansthatwhentheheatpumpshouldnormallybeabletomeettheheatingdemandonitsown,theboilerwaiting
timeapplies,butwhenthesupplysetpointissohighthattheheatpumpcannotmeettheheatingdemandonitsown,the
waiting time does not apply.
P19 Waiting Time for Boiler (default 30min.)
AhighervalueofP19willreducethenumberoftimesthattheboilerisusedatlowersupplysetpoints,butthedesired
supplytemperaturemaynotbereachedquicklyifthereisahighheatingload(slowerresponse).Conversely,alower
valueofP19willincreasethenumberoftimestheboilerisusedatlowersupplysetpoints,butensurethatthedesired
supply temperature is reached more quickly (better response).
This function disables the boiler control when the outdoor temperature is above the boiler maximum outdoor temperature
setting. Above this setting it is assumed that the heat-pump is able to deliver all the requested heat by itself and the boiler
is therefore not required.