137
System MMI Pack (Room unit and RF receiver)
SMGB0066 rev.0 - 12/2009
Controller pack
Service Manual
4
note
To ensure correct heat pump system operation, parameter “8:Su” must be set correctly. See note in section  -
Using the Room Unit for Specic Applications.
   
Heat/Cool 
selection enable 
/ disable
4:HC 0 Disabled 1
Enabled
DO NOT CHANGE
Room 
Temperature 
Sensor Use
8:Su 0
Programmer 
and room 
compensation unit
1
Programmer only. Transmits 
demand and room setpoint (no 
temperature displayed)
Maximum 
Flow Setpoint 
(extension 
systems only)
11:uF 55
55°C Maximum 
Flow Temp.
0 to 
99
0°Cto99°Cadjustmentin1°C
steps
Minimum 
Flow Setpoint 
(extension 
systems only)
12:LF 15
15°C Minimum 
Flow Temp.
0 to 
50
0°Cto50°Cadjustmentin1°C
steps
Mixing Value 
Run Time 
(extension 
systems only)
13:Ar 150 150 seconds
0 to 
240
0to240sec.adjustmentin1sec
steps
Pump Overrun 
Run Time 
(extension 
systems only)
14:Pr 15 15 minutes
0 to 
99
0to99minsadjustmentin1min
steps
note
Remember to always press the green  -
 button to conrm that you want to store your new Installer Set-Up 
setting. To exit the Installer Mode press the   or   button.
 
The binding operation described below is required if:
• Anyofthesystemcomponents(RoomUnitorRFReceiver)arereplaced.
• TheRFReceiverhasincorrectornobindingdatastored(e.g.whenpre-boundsystempackcomponentshavebeen
mismatched).
note
During the binding procedure keep approximately 1m distance between the Room Unit and the RF Receiver. -